Version: 1.36.1263.218 ( - 2016-06-21):
Changed start error message, see Elog 1702
Version: 1.33.844.217 ( - 2014-03-10):
Correted bugs:
- WUN131 - DeActivateBrake automatic cleared after 1 second - should be 30 second
Version: 1.33.798.216 ( - 2013-12-20):
New features:
- WUN131: Update to new PLC parameters for control and status - elog entry 1323
- WUN131 (Old ASTRID undulator) Add minimum allowed gap parameter, the undulator will be software limited to this setting. Rename undulator to WUN131 - elog entry 1269
Correted bugs:
- Problem with ITau when filling with short - elog entry 1312
Version: 1.33.794.215 ( - 2013-12-19):
New features:
- WUN131: Update to new PLC parameters for control and status - Waiting to be tested - elog entry 1323
Version: 1.31.457.214 ( - 2011-08-22):
Correted bugs:
- Undulator moved 10 mm with only one motor when testing undulator after move of MOXA serial box to vlan 525 - elog entry 989
Version: 1.31.391.213 (tw - 2010-10-27):
New features:
- UndulatorDevice: Implemented gap difference read - elog entry 895
Version: 1.29.341.212 (tw - 2010-02-25):
Correted bugs:
- Undulator sometimes fail, undulator thread dead, thrown an exception
Removed m_clientMonitor, moved client deletion to UnduDevThread. CATCH_AND_LOG in MoveUndulator
Version: 1.29.332.211 (tw - 2010-02-02):
New features:
- Undulator device: History on error and errStr - elog entry 797
Correted bugs:
- Undulator device: when no COM ports available move button can "hang" - elog entry 807
TW100202: Fixed correction
Version: 1.28.295.210 (tw - 2009-10-05):
Correted bugs:
- Undulator device: Encoders does not (always?) reconnect after rack power off. - elog entry 764
Version: 1.28.288.209 (tw - 2009-09-21):
Correted bugs:
- Undulator stop does not work - elog entry 754
Version: 1.28.282.208 (tw - 2009-09-17):
New features:
- Converted to new Serialport device - Device document changed - elog entry 727
- Encoder update rate is changed depending on undulator state - elog entry 746
- Undulator device: Implement 'Stop' command. - elog entry 749
Correted bugs:
- Added check for valid encoders before start of movement. - elog entry 750
Removed old comm port strings from code. Cleaned code for old outcommented code.
Version: 1.28.266.207 (tw - 2009-08-13):
Correted bugs:
- Com ports above 9 can not be created
Com port names hardwired in Undulator configuration dialog - for ports above 9, the port device name must be specified with UNC, like \\.\COM10 , hardwired into dialog. Would be better to change implementation so that port name generated from integer (using CSerialPort ConnectPort with integer input)
Version: 1.27.126.206 (tw - 2008-10-02):
First version with svn version control and code generated version numbers.
Version: 1.26.146.205 (tw - 2008-10-02):